Timetric Electric is a large manufacturer and supplier of Indoor high voltage AC vacuum load switch fuse combination switch in China. Over the years, we have been focusing on high voltage equipment and our products are competitively priced and favored by customers in South America, the Middle East, Africa and Southeast Asia. We are committed to providing quality services to customers in these regions.
Indoor high voltage AC vacuum load switch fuse combination switch, Suitable for AC 50H2, rated power 40.5kV power system, is based on GB3804 and GB16926 Designed and developed by itself, suitable for AC 50Hz, rated voltage 40.5kV network, specially designed for wind power generation and solar power generation 35kV system,can be used as an independent electrical unit in 40.5kV power system or box substation. The product has reasonable structure and simple and reliable action.
This product has the advantages of large breaking capacity, safety and reliability, long electrical life, frequent operation, less maintenance and so on. At the same time, it has an obvious isolation fracture and a ground knife with relevant closing ability. It is equipped with an electric spring operating mechanism and has remote control ability
◇ Altitude: No more than 2500m
◇ Ambient air temperature: upper limit +40℃, lower limit -25℃
◇ Relative humidity: the daily average is not more than 95%, the monthly average is not more than 90%
◇ There is no obvious pollution such as corrosion or flammable gas
◇ No frequent violent vibration
The rated parameters of load switch are shown in Table 1
Content | Unit | Vacuum load switch |
Vacuum load switch- Fuse combination appliance |
|
Rated voltage | kV | 40.5 | 40.5 | |
(1min)Rated short-time power frequency withstand voltage:Phase to phase,ground/vacuum fracture/isolation fracture |
95/118 | 95/118 | ||
185/215 | 185/215 | |||
Rated lightning impulse withstand voltage (peak):Phase to phase ground/vacuum fracture/isolation fracture |
||||
Rated frequency | Hz | 50 | 50 | |
Rated current | A | 630~1250 | 最大Max:63:80:100 | |
Rated active load breaking current | A | 630~1250 | ||
Rated no-load transformer breaking current | kA | 63~125 | 一 | |
Rated closed-loop breaking current | A | 630~1250 | 一 | |
Rated cable charging current | A | 21 | 21 | |
Rated line charging breaking current | kA | 2.1 | 2.1 | |
Rated ground fault breaking current | kA | 100 | 100 | |
Rated short-circuit closing current | kA | 50、63、80 | 一 | |
Rated peak withstand current | kA | 50、63、80 | 一 | |
Rated peak withstand current |
Load switch (including disconnecting switch) |
kA/s | 20/425/431.5/4 | 一 |
Ground switch | 20/225/231.5/2 | 一 | ||
Mechanical life (load switch/isolation switch/ground switch) | time | 5000/2000/2000 | ||
weight | kg | 245 |
Technical parameters of vacuum load switch are shown in Table 2
Content | Unit | Value |
Contact opening distance | mm | 18±1 |
overtravel | 4±1 | |
Allowable wear thickness of contact | 3 | |
Three phase division and closing are different | ms | ≤2 |
Contact closing bounce time | ≤5 | |
Average closing speed | m/s | 0.7±0.2 |
Average opening speed | 1.6±0.2 | |
Closing time(rated operating voltage) | S | ≤10 |
Opening time(rated operating voltage) | MS | ≤45 |
Loop resistance (including isolation) | μΩ | ≤180(except fuse) |
Operating mechanism parameters are shown in Table 3
Content | Unit | Value | ||
Rated voltage of energy storage motor (fluctuation range:85%~110%) | V | DC110,AC220,DC220 | ||
Rated output power of closed storage motor | W | ≤70 | ||
Energy storage time | S | ≤15 | ||
Rated operating voltage | Switching electromagnet (85%~110%) | V | AC220 | DC220 |
Rated working current | Switching electromagnet | A | 3.5 | 2.0 |
Rated maximum output power | Switching electromagnet | W | 700 | 440 |